Skip to main content
Article

Исследование причин разрушения полимерных изоляционных конструкций ЛК-120/500 и ЛК-160/500

Ахматилл Саматиллаевич КудратиллаевИнститут энергетики и автоматики Академии наук Республики Узбекистан, Узбекистан, Ташкент
ABI

Abstract

The causes of the destruction of the insulating structures LC-120/500 and LC-160/500 in quantity of 18 units under construction of overhead line 500 kV were researched. It has been shown that the bulk of the destruction occurred in the glass of ferrules of insulator as a fissure of fiberglass rod at the bottom of a glass in front of the sharp edges of the bottom of the glass of ferrules.

Not yet translated

Topics

Citations and references

Cited by 00 references