Перейти к основному содержанию
AkademIndex

Продукты

Для разработчиков

AkademBaseОткрытый API экосистемы
Статья

Frequency Domain Diagnostics of Transformer Insulation

Miroslav GuttenUniversity of ŽilinaMilan ŠebökUniversity of ŽilinaDaniel KorenčiakUniversity of ŽilinaPeter BrncalUniversity of ŽilinaM. KubiśUniversity of ŽilinaPaweł ŻukowskiLublin University of TechnologyTomasz N. KołtunowiczLublin University of Technology
2019en
ABI

Аннотация

The first part of paper deals with the base information about diagnostics of power transformers. In this part are presented differently insulating methods, for example method of recovery voltage method, method of polarization and depolarization currents and chromatographic analysis. The second part of paper deals use of method of frequency domain spectroscopy for oil power transformers. This method is used in analysis insulating condition of power transformer with system of oil-paper. It was found, that the results of these tests are highly impacted by the operating temperature during the experimental measurement. Moisture and conductivity between insulating paper and oil in an insulating system are highly dependent from temperature. In the other part, the paper presents experimental results of the frequency diagnostic measurement for a real single-phase traction transformer 110/27 kV at different operating temperatures and states (with oil and without). Finally in the last part, the paper presents comparing frequency insulating measurements among several the same single-phase transformers 110/27 kV.

Перевод пока недоступен

Идентификаторы

Цитирования и источники

Цитирований: 4Использованных источников: 0