Exact Voltage Unbalance Assessment Without Phase Measurements

Jozef GhijselenDepartment of Electrical Energy, Systems, and Automation (EESA), Faculty of Engineering, Ghent University, Ghent, BelgiumA.P.M. VandenBosscheDepartment of Electrical Energy, Systems, and Automation (EESA), Faculty of Engineering, Ghent University, Ghent, Belgium
2005en
ABI

Аннотация

In this letter, it is shown that the positive- and negative-sequence components of a three-phase, sinusoidal and unbalanced voltage system can be calculated exactly without the application of the Fortescue transformations in the complex plane, while only the root mean square (RMS) line-to-line voltages are required, and without having to measure the phase relationships between these voltages. This results in a convenient procedure to assess voltage unbalance in the field. The phase relationships between the sequence and line components can also be calculated. Moreover, if the RMS values of the line-to-neutral voltages are known, the zero-sequence component can be calculated exactly as well, again, without the application of complex mathematics.