Integrated SVC and step-down transformer model for Newton-Raphson load flow studies
Claudio R. Fuerte‐EsquivelVirtual FACTS Research Laboratory, Graduate & Research Centre in Electrical Engineering, Instituto Tecnologico de Morelia, MexicoEnrique AchaDepartment of Electronics and Electrical Engineering, The University of Glasgow, UKI. Ambriz-Perez
2000en
ABI
Аннотация
This letter presents an integrated static VAr compensator (SVC) and step-down transformer model suitable for power flow studies using the Newton-Raphson method. The SVC is taken to be a continuous, variable-shunt susceptance that is adjusted automatically to satisfy a specified voltage magnitude. The step-down transformer is represented by an admittance that combines easily with the variable susceptance, representing the SVC plant. The resulting equivalent model allows for a direct SVC voltage regulation at the high-voltage side of the transformer, which does not compromise the quadratic convergence characteristics of the Newton-Raphson method.
Перевод пока недоступен
Идентификаторы
Цитирования и источники