Diagnostic Operating-mode Control of an Oil-immersed Power Transformer Based on Cumulative Damage
Annotatsiya
The relevance of the study is associated with the transition from separate recording of individual transformer diagnostic parameters to an integrated damage assessment followed by operating-mode control. The aim was to develop and experimentally verify a diagnostic control approach for an oil-immersed power transformer based on the combined effects of switching-induced mechanical loading, vibration fatigue, and thermal insulation ageing. The study was carried out on a 20 MVA, 110/6 kV oil-immersed transformer operating at a substation of a mining and metallurgical enterprise. Continuous monitoring of vibration acceleration, hottest-spot temperature, currents, and protection operation events was combined with cumulative-damage calculation, Fisher's adequacy criterion, and reliability indices. Diagnostic control reduced protection clearing time from 80 to 50 ms, annual switching-related damage from 8.75 to 4.862%, vibration-related damage from 4.0 to 1.6%, and thermal degradation from 3.28 to 0.30%. Total annual cumulative damage decreased from 16.0 to 6.8%, the equivalent failure rate from 0.16 to 0.068 year -1 , while one-year reliability increased from 0.8521 to 0.9343. The results demonstrate that a physically interpretable combination of electrical, mechanical, and thermal degradation factors can provide a basis for real-time operating-mode control and improved transformer reliability.