Diagnostic Operating-mode Control of an Oil-immersed Power Transformer Based on Cumulative Damage

San‘at Tog‘aymurodovDepartment of Technologies, Navoi State University of Mining and Technologies, Navoi, Uzbekistan
2026en
Ochiq kirishOlmos

Litsenziya: cc-by

ABI

Annotatsiya

The relevance of the study is associated with the transition from separate recording of individual transformer diagnostic parameters to an integrated damage assessment followed by operating-mode control. The aim was to develop and experimentally verify a diagnostic control approach for an oil-immersed power transformer based on the combined effects of switching-induced mechanical loading, vibration fatigue, and thermal insulation ageing. The study was carried out on a 20 MVA, 110/6 kV oil-immersed transformer operating at a substation of a mining and metallurgical enterprise. Continuous monitoring of vibration acceleration, hottest-spot temperature, currents, and protection operation events was combined with cumulative-damage calculation, Fisher's adequacy criterion, and reliability indices. Diagnostic control reduced protection clearing time from 80 to 50 ms, annual switching-related damage from 8.75 to 4.862%, vibration-related damage from 4.0 to 1.6%, and thermal degradation from 3.28 to 0.30%. Total annual cumulative damage decreased from 16.0 to 6.8%, the equivalent failure rate from 0.16 to 0.068 year -1 , while one-year reliability increased from 0.8521 to 0.9343. The results demonstrate that a physically interpretable combination of electrical, mechanical, and thermal degradation factors can provide a basis for real-time operating-mode control and improved transformer reliability.

Hali tarjima qilinmagan

Identifikatorlar

Iqtiboslar va manbalar