Analysis Method of Testing the Time Period of Partial Discharge Symptoms on Automotive Engine Lubricant Insulation with Needle Plate Electrodes

Elih MulyanaProgram Studi Pendidikan Profesi Insinyur, Universitas Pendidikan IndonesiaMuhammad Yahya UlumudinProgram Studi Pendidikan Profesi Insinyur, Universitas Pendidikan IndonesiaRustam ErgashevTashkent Institute of Irrigation and Agricultural Mechanization Engineers, National Research University, UzbekistanDustnazar Khimmatalievik State Pedagogical University, Jl. Amir Temur, No. 104, Chirchik City, UzbekistanMukhlisa Dustnazar Kizi OmonovaPedagogy and Psychology, Alfraganus University, Tashkent shahar, Yunusobod tumani, Tklikish MFY, Yukori, Karakamish St 2a-uy, 100190, Toshkent, UzbekistanGulchexra ErgashevaTashkent Institute of Irrigation and Agricultural Mechanization Engineers, National Research University, Uzbekistan.... Teacher, Tashkent Institute of Irrigation and Agricultural Mechanisation Engineers" National Research University
ABI

Annotatsiya

Good insulation function in transformers is a major concern in the reliability of electrical energy distribution systems. Transformers serve as key components requiring effective insulation systems. This study analysis the time period of partial discharge (PD) phenomena in automotive engine oil using needle-plate electrodes with two detection components: HFCT and loop antenna. Testing was conducted 10 times with parameters including BGN on/off, positive/negative PDIV, PDIV × 1.25, and PDIV × 2. Results show automotive engine oil PDIV (2.0 kV) is lower than transformer oil (2.35 kV). PD time period in automotive oil was 6-6.4 μs, while transformer oil was 6.8 μs. Positive PDIV frequency in automotive oil (166.7 Hz) was higher than negative PDIV (156.250 Hz), while transformer oil had equal frequencies (147.1 Hz). The study concludes that PD in automotive engine oil insulation is more severe compared to transformer oil, with transformer oil demonstrating superior insulation strength. Keywords: insulation, PD, frequency, needle-plate electrode.

Mavzular

Identifikatorlar

Iqtiboslar va manbalar

0 ta iqtibos0 ta foydalanilgan manba
Koʻrsatkichlar — AkademScholar · Tez orada