Modeling and Experimental Analysis of Autonomous Power Systems with Combined Renewable Sources and Deep-Discharge Lead-Acid Batteries

Yudaev Igor ViktorovichKuban State Agrarian University, Krasnodar, Russian FederationUkraintsev Maxim MikhailovichAzov-Black Sea Engineering Institute – branch of the Don State Agrarian University in Zernograd, Zernograd, Russian FederationMartynov Aleksandr PetrovichAzov-Black Sea Engineering Institute – branch of the Don State Agrarian University in Zernograd, Zernograd, Russian FederationTursunov Shokir ChorievichTermez state university, Termez, UzbekistanKhujanazarov Sherbek FakhriddinTashkent Institute of Irrigation and Agricultural Mechanisation Engineers” National Research University, UzbekistanKozenkov Vladimir AnatolyevichAdmiral Ushakov Maritime State University, Novorossiysk, Krasnodar region, Russian Federation
ABI

Аннотация

An autonomous hybrid power system that couples renewable sources with deep-discharge lead-acid batteries (Delta HRL 12-150; Exide Sprinter P12V190) under controlled generation and load profiles was experimentally evaluated. Using a programmable DC source and an electronic load (0.1–60 A), repeated charge–discharge cycles were performed at 500–1200 W, including short overloads (+25%). Increasing discharge power reduced the effective capacity by approximately 10–12% when the load was increased from 500 W to 1000 W (e.g., decreasing from 120 to 110 Ah for Delta; and from 162 to 146 Ah for Exide). An additional capacity loss of approximately 6–8% was observed following five brief overload cycles. Localised hot spots reaching 52 °C were detected near terminal connections via thermography. The average energy efficiency was recorded at 91.2% during discharge and 89.5% during charge. A coupled power-balance and electro-thermal model (Peukert-type capacity correction with OCV–Rint voltage and a first-order thermal node) was identified from repeated runs; out-of-sample errors were MAPE(V)=3.1%, RMSE(capacity)=3.4 Ah, RMSE(temperature)=1.2 °C, and energy-balance error=1.8%. The results quantify how discharge-current-dependent capacity and case temperature jointly affect reliability and efficiency in standalone hybrid systems and provide validated parameters for supervisory control.

Темы

Идентификаторы

Цитирования и источники

Цитирований: 0Использованных источников: 0
Показатели — AkademScholar · Скоро